Weil-McLain Boiler: First-year special inspection
First-year special inspection on a Weil-McLain boiler: Extra inspection due no later than 12 months after installation.
Applies to: ECO Tec Series 3 gas boilers
Common causes of first-year special inspection
- Heavy fouling of heat exchanger or condensate lines
- Combustion air contamination
How to fix first-year special inspection: step by step
- Obtain a Weil-McLain maintenance kit before starting.
- Inspect the heat exchanger and clean if needed (p. 150).
- Inspect the cover plate insulation and gasket; replace if not in good condition.
- Inspect the burner and clean it with a vacuum and compressed air if needed.
- Make sure there is no blockage or debris in the burner or burner ports; replace the burner if needed.
- Check burner tightness. Remove cover plate insulation and tighten burner screws if needed (p. 151).
- Check the vent seals with the mirror method (p. 136).
- Disconnect the condensate trap and drain lines, inspect and flush, then reinstall and refill the trap (p. 132).
- If the heat exchanger is heavily fouled or condensate lines show sediment, schedule a follow-up inspection sooner than 12 months.
- If heavy fouling suggests combustion air contamination, inspect the air intake area and remove contaminants (p. 25).
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: ECO Tec series 3 boiler manual, p. 139. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.