Updated · by Aurora Star Tech Inc.

External high-limit and low water cutoff requirements on a Weil-McLain boiler: The U-Control provides high limit and low water protection by sensing the heat exchanger temperature. Some codes or jurisdictions require extra external controls. Use the external limit circuit on the P13 terminals when lower temperature circuits are on the system.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: All Ultra Series 4 models

How to fix external high-limit and low water cutoff requirements: step by step

  1. If ASME or Canadian requirements apply, install a manual reset high temperature limit in the supply piping between the boiler and isolation valve, set not above 200 °F.
  2. The U-Control shuts the boiler down at 195 °F, or lower if set lower.
  3. For a manual reset external limit, connect series isolated contacts to P13 terminals 1 and 2. For an automatic reset limit, use P13 terminals 3 and 4.
  4. If the U-Control is manual reset with an external manual reset limit, set the U-Control boiler limit at least 20 °F below the external limit. Example: 180 °F for a 200 °F external limit.
  5. If a low water cutoff is needed, install an electrode probe-type cutoff designed for water in a tee in the supply piping above the boiler. Wire it per the field wiring section.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Weil-McLain Boiler codes

Source: Ultra Series 4 boiler manual, p. 9. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.