Weil-McLain Boiler: External high limit setpoint and multi-temperature systems
External high limit setpoint and multi-temperature systems on a Weil-McLain boiler: Some jurisdictions require an added manual reset high limit. The control high limit shuts the boiler at 195 F or lower if set lower. The external manual reset limit must not be set above 200 F in the piping between boiler and isolation valve. Low temperature circuits such as radiant slab or PEX need their own limit controls wired to the external limit circuit. A combi in a low temperature system is multi-temperature.
Applies to: All ECO Tec Series 3 boilers
How to fix external high limit setpoint and multi-temperature systems: step by step
- Confirm local code requirement for an external high temperature limit.
- Install a manual reset high limit set no higher than 200 F, in piping between boiler and isolation valve.
- Set the control boiler limit at least 20 F below the external manual reset limit (example: control no higher than 180 F for a 200 F external limit).
- Protect low temperature circuits with limit controls wired to the control external limit circuit terminals.
- Wire the limit controls per the field wiring instructions starting on page 65.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: ECO Tec Series 3 Boiler Manual, p. 47. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.