Weil-McLain Boiler: Expansion tank connection (closed-type tank)
Expansion tank connection (closed-type tank) on a Weil-McLain boiler: Connection details for a closed-type expansion tank. An undersized tank causes water loss at the relief valve and makeup water at the fill valve, which can lead to section failure.
Applies to: Closed-type expansion tank, Figure 16
Common causes of expansion tank connection (closed-type tank)
- Undersized expansion tank.
- Tank connected at the wrong point.
How to fix expansion tank connection (closed-type tank): step by step
- Size the tank for the boiler and system water volume and temperature.
- Connect the tank to the 1/2 in. NPT tapping behind the supply outlet using 1/2 in. NPT piping.
- Pitch horizontal piping up toward the tank at 1 in. per 5 ft.
- Connect the fill line only at the expansion tank, never at another point in the system.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: EG/PEG Series 7 boiler manual, p. 21. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.