Expansion tank and make-up water sizing and piping on a Weil-McLain boiler: An undersized expansion tank lets system water escape through the relief valve and pulls make-up water in through the fill valve. Excess make-up water eventually causes boiler failure.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: All Ultra Series 4 models

Common causes of expansion tank and make-up water sizing and piping

  • Expansion tank undersized for boiler and system volume
  • Air vent operation on a closed-type tank system

How to fix expansion tank and make-up water sizing and piping: step by step

  1. Size the expansion tank for the boiler and system volume and temperature. Allow 3 gallons for the boiler and its piping.
  2. Locate the tank as shown in the manual or by a recognized design method.
  3. Connect the tank to the air separator only if the separator is on the suction side of the circulator. Install the system fill connection at the same point as the tank connection.
  4. For a diaphragm or bladder tank, install an automatic air vent on top of the air separator. If the boiler is above the main piping, also install an automatic air vent in the top of the outgoing boiler piping.
  5. For a closed-type tank, do not install automatic air vents. Pitch horizontal piping up toward the tank 1 in. per 5 ft and connect to the tank with at least 3/4 in. pipe.
  6. Do not use a closed-type expansion tank with a Weil-McLain AQUA PLUS water heater. The water heater needs an automatic air vent, and the vent would waterlog a closed-type tank.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Weil-McLain Boiler codes

Source: Ultra Series 4 boiler manual, p. 11. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.