Weil-McLain Boiler: Example F multi-boiler piping and circulator notes
Example F multi-boiler piping and circulator notes on a Weil-McLain boiler: Setup notes for the Example F multi-boiler layout with variable primary circulator and isolation/bypass valves.
Applies to: Evergreen Pro Series 2 multi-boiler installations (Example F)
How to fix example f multi-boiler piping and circulator notes: step by step
- Follow the control setting notes and use the Example F settings table as the starting point. Use the Wizard or the manual menus to enter them.
- Size the variable primary system circulator for the required flow. Pumps must deliver the flow each boiler needs.
- Follow the sizing guidelines in the manual and use sound engineering practice for the whole system.
- Provide an external relay and separate power for any boiler circulator whose load goes above 2.2 A FLA, 3.6 A locked rotor, or 16.4 A inrush.
- Provide an external relay and separate power for any system circulator whose load goes above 2.0 A FLA.
- Follow the manual's piping instructions for both the boiler and the system.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: Weil-McLain Series 2 advanced manual 550-100-581/0325, p. 40. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.