Weil-McLain Boiler: Energy-saving temperature reduction override
Energy-saving temperature reduction override on a Weil-McLain boiler: The boiler reduces water temperature as heating load drops (Section 303, 2007 Energy Act). The override that bypasses this is for use only in the listed cases.
Applies to: ECO Tec 80/110/150/199 Series 3
How to fix energy-saving temperature reduction override: step by step
- Use the override only if an external energy management system already lowers boiler water temperature as load drops.
- Use it if the boiler is not used for space heating.
- Use it if the boiler is part of a modular or multiple boiler system with total input of 300,000 BTU/hr or more.
- Do not use the override in any other case. The tankless coil condition does not apply to ECO Tec.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: ECO Tec Series 3 boiler manual, p. 184. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.