Weil-McLain Boiler: Display blank and no response to call for heat
Display blank and no response to call for heat on a Weil-McLain boiler: The control is not getting 24 VAC power.
Applies to: ECO Tec Series 3
Common causes of display blank and no response to call for heat
- Short circuit or incorrect wiring.
- Blown 3 A low voltage fuse.
- Transformer not outputting 24 VAC.
How to fix display blank and no response to call for heat: step by step
- Check wiring for shorts and correct it per the wiring diagram, including the transformer connection to the control.
- Check the 3 A low voltage fuse and replace it with the Parts section part if blown.
- If the fuse blows again, recheck wiring per the diagrams.
- Check transformer output for 24 VAC.
- Replace the transformer if it receives 120 VAC but outputs no 24 VAC.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: ECO Tec Series 3 boiler manual, p. 163. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.