Weil-McLain Boiler: Display blank and no boiler components running
Display blank and no boiler components running on a Weil-McLain boiler: The control is not getting 120 VAC power.
Applies to: ECO Tec Series 3
Common causes of display blank and no boiler components running
- Service switch or breaker off.
- No 120 VAC at the service switch or at J1.
- Blown 4 A line voltage fuse.
How to fix display blank and no boiler components running: step by step
- Confirm the service switch and circuit breaker are on.
- Check for 120 VAC at the service switch; correct the supply if none.
- Check for 120 VAC at the line voltage terminal block at J1 on the circuit board and correct wiring.
- Inspect the 4 A fuse and replace it with the Parts section part if necessary.
- If it blows again, recheck wiring per the diagrams.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: ECO Tec Series 3 boiler manual, p. 163. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.