Weil-McLain Boiler: Display backlight colours
Display backlight colours on a Weil-McLain boiler: The two-line display backlight shows operating state. No backlight means standby. Green means powered on or buttons in use, and it turns off after 20 minutes without button activity. Blue means initialization or a CH call. Purple means a DHW call. Red means an unconfigured control or an active fault.
Applies to: Unity-CI control, EG / PEG Series 7 boilers
How to fix display backlight colours: step by step
- Check backlight colour first to identify the operating state.
- On a red fault, use the Advanced Menu to view parameter states while the fault is active.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: EG / PEG Series 7 boiler manual, p. 39. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.