Weil-McLain Boiler: Direct vent: down-turned air inlet elbow
Direct vent: down-turned air inlet elbow on a Weil-McLain boiler: The air inlet is a direct vent connection, so it is not treated as a forced air intake for spacing from other vents. Its location must keep flow clear of plants and exhaust from other appliances.
Applies to: Direct vent vertical vent / sidewall air, air inlet elbow
How to fix direct vent: down-turned air inlet elbow: step by step
- Use the left-side configuration unless the terminations would fail the minimum clearance to grade or snow line.
- Use the right-side configuration when the terminations must be raised to meet the grade or snow line clearance.
- Place the air inlet at least 12 in below and 12 in horizontally from any appliance or building vent outlet.
- Keep the air inlet clear of obstructions and plants that could block air flow.
- If the air pipe runs up the building side, brace it no further than 24 in apart and keep all clearances and lengths.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: Ultra Series 4 boiler manual, p. 80. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.