Weil-McLain Boiler: Direct exhaust sidewall termination location and length
Direct exhaust sidewall termination location and length on a Weil-McLain boiler: Keep the vent exit where condensate, vapor and flue plume will not cause damage, injury or nuisance, and keep outside vent length within limits to avoid freezing.
Applies to: Direct exhaust sidewall vent
Common causes of direct exhaust sidewall termination location and length
- Outside vent length too long, condensate freezes and shuts the boiler down
- Termination above a door, window or deck
- Termination over a public walkway
How to fix direct exhaust sidewall termination location and length: step by step
- Use a down-turned elbow that butts against the outside wall plate.
- Keep the total vent piping within the maximum length in Figure 12 (allows 2 elbows; reduce for more elbows).
- Keep exposed outside pipe to 4 feet or less without an enclosure; longer runs need an enclosure that the vent exits through.
- Brace the vent pipe no more than 24 inches apart.
- In extremely cold climates, use an insulated chase that allows inspection of the vent pipe.
- Keep the termination away from shrubs, air conditioners, meters and recessed areas.
- Do not terminate above any door or window or under a deck.
- Seal the annular space around the penetration with approved material.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: Ultra Series 4 boiler manual, p. 86-87. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.