Weil-McLain Boiler: Convert propane boiler to natural gas
Convert propane boiler to natural gas on a Weil-McLain boiler: Same process as the propane conversion, using the natural gas kit and with the propane orifice removed. Natural gas boilers have no orifice.
Applies to: ECO Tec 80/110/150/199 propane to natural gas
How to fix convert propane boiler to natural gas: step by step
- Follow the propane conversion steps using the correct natural gas kit.
- Remove the propane gas orifice from between the gas pipe and the venturi.
- Set the boiler control fuel type to Natural Gas if propane was selected.
- Turn the throttle screw fully clockwise until it stops, then turn it counterclockwise the number of turns in the setting table.
- Set the control and run the full startup with a combustion analyzer.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: ECO Tec Series 3 Boiler Manual, p. 23. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.