Weil-McLain Boiler: Contaminated combustion air
Contaminated combustion air on a Weil-McLain boiler: Corrosive contaminants in the combustion air will damage the boiler. Check the air inlet location and the surrounding area before installing.
Applies to: All listed boiler series
Common causes of contaminated combustion air
- Spray cans with chloro/fluorocarbons
- Paint or varnish removers
- Permanent wave solutions
- Hydrochloric or muriatic acid
- Chlorinated waxes, cleaners, cements and glues
- Chlorine-based pool chemicals
- Anti-static fabric softeners used in dryers
- Calcium chloride used for thawing
- Chlorine bleaches, detergents and cleaning solvents
- Sodium chloride used for water softening
- Adhesives for building products
- Refrigerant leaks and excessive dust and dirt
- Nearby laundry or dry cleaning, auto body, pool, plastics, metal fabrication, refinishing, beauty shops, refrigeration repair, new construction, remodeling, photo processing or garages with workshops
How to fix contaminated combustion air: step by step
- Check the air inlet area for the listed products and areas.
- If contaminants are found, remove them permanently.
- Or isolate the boiler and provide outside combustion air.
- If the air inlet is in a contaminated area, re-pipe combustion air and vent to another location.
- Follow national, provincial or local codes.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: Gas-Fired Boilers User Manual, p. 5. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.