Weil-McLain Boiler: Connect PVC/ABS vent or air pipe to the boiler adapter
Connect PVC/ABS vent or air pipe to the boiler adapter on a Weil-McLain boiler: Use a smooth, chamfered pipe end so the adapter gasket seals. The clamp only holds the pipe; the seal comes from the internal gasket.
Applies to: Ultra boiler vent and air connectors
How to fix connect pvc/abs vent or air pipe to the boiler adapter: step by step
- Cut the pipe square, then clean and chamfer the insertion end. Deburr the inside of the insertion end and clean and deburr both ends.
- Check the adapter for obstructions or foreign objects.
- Loosen the adapter clamp screw.
- Measure 3-1/2 inches from the pipe end and mark it.
- Apply a small amount of silicone grease to the pipe end.
- Insert the pipe into the adapter and slide it down until the 3-1/2 inch mark reaches the adapter.
- Tighten the adapter clamp securely but do not overtighten.
- Do not force the pipe or bend the adapter when inserting.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: Ultra Series 4 boiler manual, p. 71. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.