Weil-McLain Boiler: Connect gas supply piping
Connect gas supply piping on a Weil-McLain boiler: Gas piping must be supported and leak-tested, and the gas valve outlet must not be adjusted.
Applies to: All Ultra models gas connection
How to fix connect gas supply piping: step by step
- Remove the jacket front panel and pipe gas to the boiler per Figure 33.
- Install a ground joint union for service where required.
- Install a manual shutoff valve outside the jacket where local code or the utility requires it. In Canada, the installer must identify the main manual shutoff valve.
- For wall-mounted boilers, follow the separate wall-mounting instructions; gas may enter from the bottom.
- Support the piping with hangers, not by the boiler or its accessories.
- Use two wrenches so the boiler gas connection does not turn.
- Purge all air from the gas supply piping.
- Check the boiler and its gas connection for leaks before operation.
- Check the inlet pressure at the test port (Figure 39, 40 or 41, pages 40-41).
- Do not adjust or measure the gas valve outlet pressure; the valve is factory set for natural gas and propane.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: Weil-McLain Ultra Series 4 boiler manual, p. 29. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.