Weil-McLain Boiler: Condensate trap has dried out (flue gas at drain)
Condensate trap has dried out (flue gas at drain) on a Weil-McLain boiler: With the boiler running, flue gas coming out of the condensate drain means the trap is dry and must be refilled. Flue gas in the room is a safety hazard.
Applies to: Models with condensate drain system
Common causes of condensate trap has dried out (flue gas at drain)
- Vent system not making enough condensate to keep the trap full
- Obstruction in the condensate drain line
How to fix condensate trap has dried out (flue gas at drain): step by step
- Make sure the boiler is running and hold a finger near the drain tube outlet to feel for flue gas.
- Remove the trap and pour fresh water into it until water runs out the far end of the drain line.
- If no water comes out, there is a blockage: loosen the flexible drain hose and trap inlet connection.
- Remove and flush the trap and drain line, then reinstall and tighten all connections.
- Pour water in again and confirm it runs out the drain end.
- If water still does not come out, call a qualified technician to clean or replace the condensate assembly.
- If the trap dries out regularly, have a technician inspect the boiler and condensate line.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: Gas-Fired Boilers User Manual 550-100-226/0425, p. 19. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.