Weil-McLain Boiler: Concentric 3 in or 4 in sidewall termination: kit and piping rules
Concentric 3 in or 4 in sidewall termination: kit and piping rules on a Weil-McLain boiler: The concentric termination kit is purchased separately and must match the materials and adapters in Figure 12. The maximum-length allowance covers one elbow.
Applies to: Ultra boilers with concentric sidewall termination
How to fix concentric 3 in or 4 in sidewall termination: kit and piping rules: step by step
- Buy the 3 inch or 4 inch concentric termination kit separately.
- Use only the vent materials and kits listed in Figure 12 on page 18 and add the adapters it specifies.
- Use only the materials listed in Figure 13 on page 19.
- Keep the total air plus vent length from the boiler to the termination within the Figure 12 maximum. Each elbow beyond the allowance reduces the maximum length per the table notes.
- Connect from the termination to the boiler on page 82.
- The air and vent centerlines are wider at the termination than at the boiler. Use the spacing method in Figure 87 on page 77 if needed.
- You may rotate the Y-fitting slightly to raise or lower the air pipe, but the centerlines must still match the boiler vent and air connections.
- Install a bird screen at each termination. Most kits do not include them; buy them separately from WM Technologies or the vent kit supplier.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: Ultra Series 4 boiler manual, p. 72. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.