Updated · by Aurora Star Tech Inc.

Combustion check at high and low fire on a Weil-McLain boiler: Check flame and combustion with calibrated instruments at high and low fire.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Ultra Series 4 gas boilers

Common causes of combustion check at high and low fire

  • Throttle screw position out of range
  • Gas input off rating

How to fix combustion check at high and low fire: step by step

  1. Start a call for heat on one heat demand input.
  2. Enter installer menus and force firing rate to MAX (high fire).
  3. Look through the flame inspection window: flame should be blue and stable with the burner surface covered in orange dots.
  4. Remove the flue temperature sensor and insert a combustion test probe.
  5. Test CO2 (or O2) and CO. CO2 must be within 1.0% of the values in Figure 42, page 41.
  6. If out of range, adjust the throttle screw as described on page 41.
  7. Measure natural gas input (see gas input tip) and compare with the boiler rating label.
  8. Force firing rate to MIN (low fire); flame should be stable, evenly spread, with uniform orange colour. Repeat the CO2 and CO test.
  9. Force firing rate back to AUTO.
  10. Refit the flue gas sensor: insert the rubber grommet into the flue pipe, then insert the probe into the grommet.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Weil-McLain Boiler codes

Source: Weil-McLain Ultra Series 4 boiler manual, p. 40. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.