Weil-McLain Boiler: Combustion air and vent piping rules at the boiler
Combustion air and vent piping rules at the boiler on a Weil-McLain boiler: The air inlet must be piped unless a Weil-McLain Direct Exhaust kit is used and its requirements are met. The air inlet connection at the boiler is 3" PVC only. The vent may use 3" PVC, CPVC, stainless or polypropylene, with approved adapters.
Applies to: ECO Tec Series 3 vent and air piping
How to fix combustion air and vent piping rules at the boiler: step by step
- Pipe combustion air to the boiler air intake, not a room air opening, unless using the Direct Exhaust kit.
- Use 3" PVC at the air inlet connection.
- Use a 3" transition at the boiler if running 2" pipe.
- Use only approved adapters; a PP adapter with its own seal that interferes with the boiler seal must not be used.
- Use a tapered reducer with a 3" PVC nipple (at least 6" long) for 3" to 2" transitions. Do not use a bushing.
- Use only the approved parts listed in the parts section (Figure 152, page 171).
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: ECO Tec series 3 boiler manual, p. 26. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.