Weil-McLain Boiler: Clean cast aluminum heat exchanger, water side
Clean cast aluminum heat exchanger, water side on a Weil-McLain boiler: Water-side cleaning for the aluminum heat exchanger. Trisodium phosphate (TSP) must not be used because it strips the protective oxide layer.
Applies to: ALL Ultra Series 4 models
How to fix clean cast aluminum heat exchanger, water side: step by step
- Use ONLY Sentinel X400 from WM Technologies. Do not use TSP or other high-pH cleaners.
- Follow the complete startup procedure beginning on page 35 after cleaning.
- After using the cleaning tool on the pin side, spray water downward from above the pins to flush sediment.
- Remove sediment from the bottom of the heat exchanger.
- Disconnect the condensate line at the bottom of the heat exchanger, place a pan under the trap connection, and spray water into the heat exchanger bottom to flush sediment to the condensate outlet.
- Spray water through the condensate line, then reconnect it.
- Reinstall the burner and cover per the access procedure for the model.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: Ultra Series 4 boiler manual, p. 125. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.