Updated · by Aurora Star Tech Inc.

Clean and test float-type low water cutoff on a Weil-McLain boiler: Clears sediment from the float chamber and checks the float-type low water cutoff shuts the boiler off at low water.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: EG and PEG steam boilers with float-type LWCO

Common causes of clean and test float-type low water cutoff

  • Sediment in the float chamber

How to fix clean and test float-type low water cutoff: step by step

  1. Make sure boiler pressure is low to avoid steam burns.
  2. Open the blowdown valve on the bottom control and drain the water into a bucket.
  3. Turn the operating control to call for heat.
  4. Before the water gets hot, drain the boiler to the bottom of the gauge glass. The boiler should shut off after the water level drops a few inches.
  5. Refill the boiler to the correct waterline. The boiler should come back on.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Weil-McLain Boiler codes

Source: Weil-McLain EG/PEG Series 7 Boiler Manual, p. 70. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.