Weil-McLain Boiler: Clean and test float-type low water cutoff
Clean and test float-type low water cutoff on a Weil-McLain boiler: Clears sediment from the float chamber and checks the float-type low water cutoff shuts the boiler off at low water.
Applies to: EG and PEG steam boilers with float-type LWCO
Common causes of clean and test float-type low water cutoff
- Sediment in the float chamber
How to fix clean and test float-type low water cutoff: step by step
- Make sure boiler pressure is low to avoid steam burns.
- Open the blowdown valve on the bottom control and drain the water into a bucket.
- Turn the operating control to call for heat.
- Before the water gets hot, drain the boiler to the bottom of the gauge glass. The boiler should shut off after the water level drops a few inches.
- Refill the boiler to the correct waterline. The boiler should come back on.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: Weil-McLain EG/PEG Series 7 Boiler Manual, p. 70. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.