Weil-McLain Boiler: Circulator zoning with a DHW zone
Circulator zoning with a DHW zone on a Weil-McLain boiler: Each zone gets its own circulator. The boiler circulator must serve only the boiler loop. An AQUA PLUS 60 can be wired as zone 1 at the U-Control.
Applies to: Circulator zoning with AQUA PLUS DHW
How to fix circulator zoning with a dhw zone: step by step
- Install a separate circulator for each zone.
- Do not use a closed-type expansion tank with an AQUA PLUS water heater.
- Wire the AQUA PLUS 60 aquastat to U-Control P11, pins 4 and 5.
- Wire the DHW circulator to U-Control P2, terminals 1, 4 and 7 (H, N, G).
- Wire the zone pumps to a two-zone circulator relay.
- Wire the circulator relay end switch to U-Control P15, pins 1 and 2.
- Set Priority 1 to DHW system, not DHW direct.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: Ultra Series 4 boiler manual 550-100-440/1025, p. 53. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.