Weil-McLain Boiler: Circulator output load limits
Circulator output load limits on a Weil-McLain boiler: Each 120VAC pump output handles only 2.2 A. Larger circulators need a relay or starter, with only the relay coil wired to the boiler terminal.
Applies to: Output 1, 2 and 3 circulator and auxiliary loads
How to fix circulator output load limits: step by step
- Check the circulator amp rating before connecting it to Output 1, 2 or 3.
- If the circulator draws more than 2.2 A, install a circulator relay or starter.
- Connect only the 120VAC coil to the boiler circulator terminals.
- Use an isolation relay if a device needs a different voltage or an isolated contact.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: SVF Series 1 boiler manual, p. 58. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.