Weil-McLain Boiler: Chimney and vent termination requirements
Chimney and vent termination requirements on a Weil-McLain boiler: Vent must follow NFPA 54 and local codes. Chimneys and non-Type B vents must extend at least 3 ft above the roof penetration and 2 ft above any building within 10 ft. Type B vents with a listed cap may end as shown in Figure 3 if at least 8 ft from a vertical wall. Otherwise Type B vents must end at least 2 ft above the roof and 2 ft above any building within 10 ft. Keep vent and air intake areas clear of snow.
Applies to: EG and PEG venting
Common causes of chimney and vent termination requirements
- Cold masonry chimney condensation damaging the masonry
- Vent termination too close to a wall or roof obstruction
How to fix chimney and vent termination requirements: step by step
- Check the chimney is lined. A lined chimney is preferred and required by some codes.
- Use a corrosion-resistant liner such as AL29-4C single-wall stainless or a correctly sized B-vent in cold masonry chimneys.
- Provide a drain trap in cold masonry chimneys to remove condensate.
- For shared chimneys, size the common vent to equal the largest appliance vent outlet plus 50 percent of each additional appliance outlet.
- Confirm the vent height and clearance above grade or snow line.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: EG / PEG Series 7 Boiler Manual, p. 11 (see Ratings table p. 89 for minimum vent sizes). Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.