Weil-McLain Boiler: Chilled water system piping
Chilled water system piping on a Weil-McLain boiler: The chilled medium is piped in parallel with the boiler and kept out of the boiler with valves.
Applies to: Chilled water systems
How to fix chilled water system piping: step by step
- Pipe the chilled medium in parallel with the heating boiler.
- Install valves that keep the chilled medium out of the boiler, with balancing and check valves as shown.
- If the coils are in air handlers exposed to refrigerated air, add flow control valves or another automatic means to stop gravity circulation during cooling.
- Use a separate circulator for the chilled water loop if the space heating system is zoned with circulators.
- Consider antifreeze effects on circulator sizing and DHW performance.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: Ultra Series 4 boiler manual 550-100-440/1025, p. 55. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.