Weil-McLain Boiler: Chemical cleaning of the domestic hot water circuit
Chemical cleaning of the domestic hot water circuit on a Weil-McLain boiler: Connect a circulating pump with chemical to the DHW cold inlet and DHW outlet, clean, rinse and restore the boiler.
Applies to: 80/110/150/199 Series 3
How to fix chemical cleaning of the domestic hot water circuit: step by step
- Shut down the boiler: follow the 'To Turn Off Gas to Appliance' instructions and close the boiler manual gas valve.
- Close the cold water inlet valve ahead of the boiler inlet.
- Release residual pressure by opening a hot tap downstream of the boiler, then close the DHW outlet valve.
- Connect the cleaning pump hoses to the cold water inlet and the DHW outlet.
- Fill the pump tank with NSF-approved descaling chemical.
- Circulate the fluid through the DHW circuit. Reverse flow by moving the pump to the DHW outlet hose if needed.
- At the end of the cycle, empty the pump and dispose of the spent solution.
- Fill the pump with water and flush out the chemical; repeat if necessary.
- Disconnect the pump hoses and reopen the cold water inlet valve.
- Restore electrical power and turn the boiler on.
- Check boiler operation and DHW production.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: ECO Tec series 3 boiler manual, p. 155. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.