Weil-McLain Boiler: Checking the CGa boiler out temperature sensor
Checking the CGa boiler out temperature sensor on a Weil-McLain boiler: How to test the outlet thermistor and the control's reading.
Applies to: CGa-25 to CGa-8, natural gas (config #15) and propane (config #5)
Common causes of checking the cga boiler out temperature sensor
- Sensor out of range
- Damaged wiring
- Control misreading
How to fix checking the cga boiler out temperature sensor: step by step
- Turn off power to the boiler before unplugging connectors or measuring resistance.
- Unplug the sensor and measure resistance with an ohmmeter.
- Easy reference points: ice water (32°F) about 293,920-374,080 ohms; room temperature 68°F about 110,414-140,526 ohms; 77°F about 88,000-112,000 ohms; boiling water (212°F) about 5,605-7,133 ohms.
- Far outside the range for the temperature: replace the sensor.
- To check the control itself, put a resistance decade box in place of the sensor and see if the display shows the matching temperature.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: Weil-McLain CGa Series 4 Boiler Manual 550-100-223/0425, Table 10 Sensor resistance values, p.63 (table text is jumbled in the export: check the values on the page). Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.