Weil-McLain Boiler: Checking boiler temperature sensors
Checking boiler temperature sensors on a Weil-McLain boiler: Boiler In, Boiler Out, DHW Out, Flue, Outdoor and System Supply/Return sensors are all resistance type. Compare measured resistance with the sensor resistance table.
Applies to: 80/110/150/199 Series 3
Common causes of checking boiler temperature sensors
- Sensor out of range versus the resistance table
- Control reading a temperature that does not match the input resistance
How to fix checking boiler temperature sensors: step by step
- Set an ohmmeter and measure sensor resistance at known temperatures: ice point (32°F), room temperature (60°F and 70°F) and boiling point at sea level (212°F).
- For ice point and boiling point, submerge the sensor in water at that temperature.
- For dual sensors, make sure the temperature difference between the two sensors is no more than 10°F.
- Compare the reading against the sensor resistance table. The table does not list 212°F.
- To check control sensing, connect a resistance decade box temporarily in place of a sensor and read the temperature on the control display. It should match the value for that resistance.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: ECO Tec series 3 boiler manual, p. 160. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.