Weil-McLain Boiler: Check water system pressure and air vents
Check water system pressure and air vents on a Weil-McLain boiler: Confirm cold fill pressure and that system pressure stays in range while heating.
Applies to: ECO Tec Series 3 boiler systems
Common causes of check water system pressure and air vents
- Expansion tank problem
- Air in system
How to fix check water system pressure and air vents: step by step
- Check cold fill pressure (usually around 12 PSIG).
- Watch system pressure as the boiler heats up. Excessive rise points to expansion tank sizing or performance.
- Remove air vent caps and briefly press the push valve to flush. Reinstall caps.
- Replace any leaking automatic air vents.
- Check water chemistry: pH, hardness and inhibitor level (p. 130-131).
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: ECO Tec series 3 boiler manual, p. 141. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.