Weil-McLain Boiler: Check the combi 3-way valve and DHW function
Check the combi 3-way valve and DHW function on a Weil-McLain boiler: Applies to combi models only. Cycle the 3-way valve by calling for space heat, then calling for domestic hot water at a faucet. The valve and boiler should switch from space heating to domestic and hot water should be delivered. If the change does not happen, run the 3-way valve test listed on page 143. Also check for water leaks at the 3-way valve, the brazed plate and the brazed plate manifold fittings.
Applies to: Combi models only
How to fix check the combi 3-way valve and dhw function: step by step
- Start a space heating call to the boiler.
- Open a domestic hot water faucet to create a DHW call.
- Confirm the valve and boiler operation change to domestic and hot water is delivered.
- If the change does not happen, run the 3-way valve test on page 143.
- Check the 3-way valve, brazed plate and manifold fittings for leaks.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: ECO Tec series 3 boiler manual, p. 144. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.