Check temperature sensors (resistance method) on a Weil-McLain boiler: All boiler sensors (flue, outdoor, return water, supply water) are resistance type. Compare measured ohms with Figure 123.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Ultra 80, 105, 155, 230, 299, 399

Common causes of check temperature sensors (resistance method)

  • Out-of-range sensor resistance
  • Wrong sensor reading on the display

How to fix check temperature sensors (resistance method): step by step

  1. Measure sensor resistance at known temperatures: 32 °F (ice point), 60 °F, 70 °F and 212 °F (boiling point at sea level). For ice and boiling points, put the sensor in water at that temperature.
  2. Use an ohmmeter and compare with Figure 123 (page 116).
  3. To check the control, connect a resistance decade box in place of the sensor and confirm the U-Control temperature matches the resistance.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Weil-McLain Boiler codes

Source: Ultra Series 4 gas-fired water boiler manual, p. 116. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.