Weil-McLain Boiler: Check temperature sensors
Check temperature sensors on a Weil-McLain boiler: Sensors (flue, outdoor, boiler in, boiler out, return, system) are resistance type. Compare readings to the sensor table.
Applies to: SVF 1500-3000 Series 1 boiler
Common causes of check temperature sensors
- Sensor drifted or failed
- Wiring or connector fault
How to fix check temperature sensors: step by step
- Turn off power to the boiler.
- Measure sensor resistance with an ohmmeter at known temperatures: 32°F ice water, 60°F or 70°F room temperature, 212°F boiling water.
- Compare readings to the sensor resistance table (page 101).
- To check the control, connect a resistance decade box in place of a sensor and confirm the displayed temperature is close to the matching value.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: Weil-McLain SVF Series 1 boiler manual, p. 100-101. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.