Weil-McLain Boiler: Check ignition system safety shutoff
Check ignition system safety shutoff on a Weil-McLain boiler: Confirms the ignition lockout works. Done after installation.
Applies to: SVF 1500-3000
How to fix check ignition system safety shutoff: step by step
- Turn the boiler off.
- Close the manual gas valve downstream of the gas valve.
- Turn the boiler on. It will try to ignite and not light.
- Confirm lockout occurs and the display shows Ignition Fault. SVF 1500/2000/2500 retry once; SVF 3000 locks out after one failure.
- Clear the lockout with Manual Reset in the Diagnostic Menu.
- Open the manual gas valve again.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: SVF Series 1 boiler manual, p. 89. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.