Weil-McLain Boiler: Check ignition cable and ground wiring
Check ignition cable and ground wiring on a Weil-McLain boiler: Verify ignition cable resistance and ground continuity.
Applies to: ECO Tec Series 3 gas boilers
Common causes of check ignition cable and ground wiring
- Ignition cable out of range
- Poor ground connection
How to fix check ignition cable and ground wiring: step by step
- Measure ignition cable resistance. A good cable reads between 950 and 1050 ohms. Replace if outside this range.
- Inspect the ground wire from the heat exchanger access cover to the ground terminal screw.
- Check ground continuity with a continuity meter.
- Replace the ground wires if results are not satisfactory.
- Verify all wiring is in good condition and securely attached.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: ECO Tec series 3 boiler manual, p. 142. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.