Weil-McLain Boiler: Check if a reservoir pipe is needed on a steam return
Check if a reservoir pipe is needed on a steam return on a Weil-McLain boiler: Modern steam boilers steam for less time than older boilers. If the condensate return takes longer than the steaming time, the boiler can overfill with an auto feed or cycle off on a low water cutoff. Use this test on an existing residential system to find out whether a reservoir pipe is needed.
Applies to: Residential EG/PEG steam boilers during replacement
Common causes of check if a reservoir pipe is needed on a steam return
- Condensate return time is longer than the boiler steaming time on a replacement boiler
How to fix check if a reservoir pipe is needed on a steam return: step by step
- Disconnect the condensate return line at the existing boiler.
- Heat the boiler and let it steam for 10 minutes, then turn it off.
- Measure the time from when the boiler starts steaming to when condensate begins to return.
- Measure the time from when condensate starts returning to when it stops; divide this time by 2.
- Add the time from the first measurement to the calculated value. This is the average condensate return time.
- If the total is 10 minutes or less, no reservoir pipe is needed.
- If the total is more than 10 minutes, install a reservoir pipe as shown in Figure 23, sized from Table 8.
- For larger systems listed in Table 8, use a boiler feed system with a condensate tank and feed pump, sized from Table 9.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: EG/PEG Series 7 boiler manual, p. 26. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.