Weil-McLain Boiler: Check heat exchanger, vent seals and condensate dish joint for leaks
Check heat exchanger, vent seals and condensate dish joint for leaks on a Weil-McLain boiler: Find leaks at the top of the boiler using a mirror at high fire.
Applies to: ECO Tec Series 3 gas boilers
Common causes of check heat exchanger, vent seals and condensate dish joint for leaks
- Loose retaining screws or nuts
- Damaged gasket at a joint
How to fix check heat exchanger, vent seals and condensate dish joint for leaks: step by step
- Run the boiler on high fire.
- Move an inspection mirror around all heat exchanger joints, vent connections and the condensate dish joints.
- A leak shows as vapor on the mirror; also look for weeping or other signs.
- If a leak is found, shut the boiler down immediately.
- Tighten the retaining screws or nuts without over-tightening.
- If still leaking, disassemble that joint, inspect the gasket and replace any damaged gasket.
- Contact WM Technologies Technical Services if the problem is not solved.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: ECO Tec series 3 boiler manual, p. 136. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.