Weil-McLain Boiler: Check flue gas temperature versus return temperature
Check flue gas temperature versus return temperature on a Weil-McLain boiler: Flue gas should not run far above the boiler return temperature at high fire.
Applies to: ECO Tec Series 3 gas boilers
Common causes of check flue gas temperature versus return temperature
- Fouled heat exchanger
How to fix check flue gas temperature versus return temperature: step by step
- Set the boiler to high fire.
- Use the control display to view flue gas temperature and boiler return temperature.
- Flue gas should be no more than 50°F above return temperature.
- If the difference is higher, clean the heat exchanger (see maintenance, p. 151).
- If the flue temperature is higher still, shut down, let cool, and clean the heat exchanger.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: ECO Tec series 3 boiler manual, p. 143. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.