Weil-McLain Boiler: Check control module and circulator/blower fuses
Check control module and circulator/blower fuses on a Weil-McLain boiler: Check fuses before replacing the control module or major components such as the blower. A blown fuse can keep the control or components from running.
Applies to: SVF 1500-3000 Series 1 boiler
Common causes of check control module and circulator/blower fuses
- Blown control, circulator or blower fuse
How to fix check control module and circulator/blower fuses: step by step
- Turn off power at the external line switch.
- Remove the top front slate panel, slide the glossy black panel up, remove the middle slate panel (two screws), and remove the control box cover (three screws).
- Remove and inspect the two control fuses and the expansion module fuse.
- Replace any blown fuse with the specified type and rating only. Never jumper a fuse.
- Inspect the boiler circulator and blower fuses and replace any blown fuse with the specified rating.
- Reinstall the control box cover (three screws), middle panel (two screws), glossy black panel and top slate panel.
- Restore power at the external line switch and verify operation.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: Weil-McLain SVF Series 1 boiler manual, p. 100. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.