Weil-McLain Boiler: Check blower speeds in manual test mode
Check blower speeds in manual test mode on a Weil-McLain boiler: Confirm blower rpm at low, ignition and high fire against the firing rate tables.
Applies to: ECO Tec Series 3 gas boilers
How to fix check blower speeds in manual test mode: step by step
- Set the correct altitude in the boiler setup menu first.
- Go to DIAGNOSTICS, then Manual test mode.
- Set the firing rate to LOW and record the blower rpm. It should be within 50 rpm of the Figure 125 (NG) or 126 (LP) value, unless low fire was raised for priority need.
- Set the firing rate to IGNITION and record rpm. It should be within 50 rpm of the Figure 125 or 126 value.
- Set the firing rate to HIGH and record rpm. It should be within 50 rpm of the Figure 125 (NG), 126 (LP) or 127 (199 NG/LP) value.
- If any value is outside range, contact the factory.
- Changing min or max blower speeds affects AFUE ratings.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: ECO Tec series 3 boiler manual, p. 142-143. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.