Weil-McLain Boiler: Check blower speeds
Check blower speeds on a Weil-McLain boiler: Compare blower RPM at each firing rate with the blower speed table (Figure 79, page 88).
Applies to: SVF 1500-3000 Series 1 boiler
How to fix check blower speeds: step by step
- For altitude above 5,500 ft, enable high altitude in the boiler setup menu. Below 5,500 ft, do NOT enable it.
- Open Manual test mode on the control display (see page 80).
- Set the firing rate to Low. Record the blower RPM and compare with Figure 79.
- Set the firing rate to MEDIUM (ignition rate). RPM should be within 200 RPM of the table value.
- Set the firing rate to High. RPM should be within 200 RPM of the table value.
- If any value is out of range, contact the factory for technical help.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: Weil-McLain SVF Series 1 boiler manual, p. 98. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.