Weil-McLain Boiler: CGa pilot ignition sequence and lockout reset
CGa pilot ignition sequence and lockout reset on a Weil-McLain boiler: What the control does on a call for heat, so you know where it is stuck.
Applies to: CGa-25 to CGa-8, natural gas (config #15) and propane (config #5)
Common causes of cga pilot ignition sequence and lockout reset
- Vent damper end switch not making
- Pilot not proving
- Propane lockout after failed tries
How to fix cga pilot ignition sequence and lockout reset: step by step
- On a call for heat the control may first just run the circulator to use stored heat before firing.
- Then the vent damper and circulator come on. Ignition only starts once the damper end switch makes.
- The control sparks and opens the pilot valve. Once flame is proven, spark stops and the main valve opens.
- Natural gas: no pilot in 15 seconds = valve closes, wait 5 minutes, try again. This repeats with no limit.
- Propane: no pilot in 15 seconds = wait 1 minute and try again, then 2 more tries with 5 minutes between. After that it locks out and needs a manual reset.
- Losing flame while running sends it back to pilot ignition. A limit trip closes the main valve but keeps the circulator and damper open.
- Manual reset: on the fault screen press Enter, change NO to YES with the arrows, press Enter. The screen turns green when it clears (only if the problem is gone).
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: Weil-McLain CGa Series 4 Boiler Manual 550-100-223/0425, Operation - Spark-ignited pilot system, p.37; Errors and lockouts, p.64. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.