Weil-McLain Boiler: Category II venting requirements

Updated · by Aurora Star Tech Inc.

Category II venting requirements on a Weil-McLain boiler: The SVF 1500 to 3000 can run as Category II (negative pressure, likely to condense) in addition to Category IV. Category II needs an engineered vent system designed by a professional and vertical termination only.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: SVF 1500, 2000, 2500, 3000 in Category II

Common causes of category ii venting requirements

  • Positive pressure in a Category II vent system causes flue gas spillage and CO emissions

How to fix category ii venting requirements: step by step

  1. Have a professional design the vent system to local authority requirements.
  2. Use vertical vent termination only.
  3. Do not connect to an existing common vent with other appliances.
  4. Supply combustion air from the boiler room with direct exhaust openings, see page 33.
  5. Install 3 ft of straight 8-inch or 10-inch pipe directly after the vent adapter, before any diameter or direction change.
  6. Keep negative pressure at the boiler outlet within the Table 2 range during all firing rates.
  7. Keep flue gas temperature at or below 210 deg F. The boiler shuts down and recycles above 210 deg F and starts to reduce firing rate at 200 deg F.
  8. Expect flue gas temperature about 20 to 30 deg F above return water temperature. Use the lowest expected return temperature for calculations.
  9. Install a CO detector in the boiler room on the same electrical circuit as the boiler, and check local code for more requirements.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Weil-McLain Boiler codes

Source: SVF Series 1 Boiler Manual, p. 29. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.