Weil-McLain Boiler: Category II negative pressure aids: fan, damper and spill switch
Category II negative pressure aids: fan, damper and spill switch on a Weil-McLain boiler: Where natural draft cannot keep the required negative pressure at the boiler outlet, Weil-McLain recommends added draft or flow control devices. Improper positive pressure can cause CO spillage.
Applies to: Category II vent systems
Common causes of category ii negative pressure aids: fan, damper and spill switch
- Higher efficiency of the SVF gives lower exhaust temperatures and less natural draft
How to fix category ii negative pressure aids: fan, damper and spill switch: step by step
- If natural draft cannot hold the negative pressure range, consider a variable speed chimney fan or power venter.
- Wire a flow proving switch into the closure switch on terminal block P11.
- Consider a double acting barometric damper or modulating damper to hold the negative pressure range.
- When using any damper, add a thermal spill switch to detect exhaust flow into the boiler room.
- Confirm the thermal spill switch temperature range suits the SVF flue gas temperature.
- Let the system designer set the spill switch set-point per local authority requirements.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: SVF Series 1 Boiler Manual, p. 30. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.