Weil-McLain Boiler: Burner flame and flame signal check
Burner flame and flame signal check on a Weil-McLain boiler: Check the flame and the flame signal reading in the U-Control.
Applies to: Ultra Series 4 boilers
Common causes of burner flame and flame signal check
- Fouled or damaged ignitor if flame signal is low
How to fix burner flame and flame signal check: step by step
- Look at the flame through the observation window (see p. 40) at high fire and low fire.
- If flame is unsatisfactory at either rate, shut off and let the boiler cool. Remove the burner and clean it with a vacuum or compressed air. Do not use compressed air indoors.
- To access the burner, remove the heat exchanger cover plate (p. 125).
- When reinstalling, check the burner gasket is in good condition and correctly positioned. Tighten the three retainer screws, then bend up the retainer tabs.
- Reattach the cover plate (see p. 126 or p. 127). Reinstall components and retest.
- Go to Diagnostics/Inputs on the U-Control and read the flame signal.
- Flame signal must be at least 20 above the shutdown value for the model (see flame signal table).
- If the signal is low, the U-Control raises firing rate to compensate. A low signal may mean a fouled or damaged ignitor. Clean it. If cleaning does not help and ground wiring and continuity are good, replace the ignitor.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: Ultra Series 4 gas-fired water boiler manual, p. 112. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.