Weil-McLain Boiler: Antifreeze use in hydronic systems
Antifreeze use in hydronic systems on a Weil-McLain boiler: Use only antifreeze made for hydronic systems; inhibited propylene glycol is recommended. Ethylene glycol, automotive or undiluted antifreeze must not be used. A 50% propylene glycol/water solution gives protection to about -30°F. Boiler water content is listed on page 89 and the expansion tank volume must be included.
Applies to: Freeze protection in water boilers
How to fix antifreeze use in hydronic systems: step by step
- Calculate antifreeze quantity from total system water content, including the expansion tank.
- Follow the antifreeze manufacturer's instructions.
- If an automatic fill is used, install a water meter to monitor makeup water because glycol leaks before water does.
- If freeze protection or circulator exercising is not used, disable FREEZE PROTECT in the ADVANCED MENU under CIRCULATOR settings.
- Install a backflow preventer or disconnect from city supply if local codes require it.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: EG / PEG Series 7 boiler manual, p. 56. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.