Weil-McLain Boiler: Additional limit controls and external limit wiring
Additional limit controls and external limit wiring on a Weil-McLain boiler: ASME installations may need a manual reset high temperature limit in the supply piping. Systems with low-temperature circuits should protect them with external limits wired to the Unity-CI control P4 terminals.
Applies to: EG / PEG Series 7 water boilers
How to fix additional limit controls and external limit wiring: step by step
- If ASME applies, install a manual reset high temperature limit in the system supply piping between the boiler and its isolation valve. Set it to no more than 240°F.
- Note that the Unity-CI operating limit shuts the boiler down at 210°F or lower, depending on the set value.
- For a manual reset external limit, wire series isolated contacts to P4 terminal 1 by cutting and splicing at mark ‹1›.
- For an automatic reset external limit, wire series isolated contacts to P4 terminal 3 by cutting and splicing at mark ‹2›.
- If a manual reset limit is used, set the Unity-CI boiler limit at least 20°F below the external manual reset limit (for example, no higher than 180°F for a 200°F external limit).
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: EG / PEG Series 7 boiler manual, p. 33. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.