Weil-McLain Boiler: Access and clean exchanger, Ultra-155, -230, -299 and -399

Updated · by Aurora Star Tech Inc.

Access and clean exchanger, Ultra-155, -230, -299 and -399 on a Weil-McLain boiler: Removes the blower, venturi, gas valve and cover plate as one assembly; the burner is removed from the cover plate for cleaning.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Ultra-155, -230, -299 and -399 only

How to fix access and clean exchanger, ultra-155, -230, -299 and -399: step by step

  1. Close the external manual gas valve.
  2. Disconnect: gas valve electrical plug, two molex plugs from the blower assembly, ignition cable and ground wire.
  3. Disconnect the flexible gas line at its flare fitting.
  4. Lift the plastic clamp off the gas line and slide the air silencer off the valve.
  5. Remove the hex nuts (10 mm) from the cover plate and remove the burner cover plate from the heat exchanger.
  6. Pull the blower/venturi/gas valve/cover plate assembly out of the boiler.
  7. Remove the three M4 hex screws (7 mm) and burner clips holding the burner to the cover plate; remove the cover plate.
  8. Vacuum the heating surfaces. Do not use solvent. If needed, wash with clean warm water and use the cleaning tool or thin sheet metal as above.
  9. Inspect cover plate insulation and gasket; replace if damaged.
  10. Reinstall the burner with the screws and clips removed earlier.
  11. Place the cover plate gasket in the groove and replace the cover plate.
  12. Tighten the nuts in a staggered pattern, then in two or three passes to the sequence in Figure 128; final torque must not exceed 50 in-lb (±10 in-lb).
  13. Reinstall the air silencer over the gas valve venturi and secure the clamp.
  14. Reconnect wiring, flexible gas line and gas valve plug.
  15. Perform a soap suds leak test on all interior gas piping after starting the boiler.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Weil-McLain Boiler codes

Source: Ultra Series 4 boiler manual, p. 127. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.