Weil-McLain Boiler: 0-10VDC output for lead/lag and variable speed pump
0-10VDC output for lead/lag and variable speed pump on a Weil-McLain boiler: The 0-10VDC output can drive lead/lag systems or a variable speed boiler pump.
Applies to: Evergreen 110/155/220/299/300/399
How to fix 0-10vdc output for lead/lag and variable speed pump: step by step
- For lead/lag, set MAX RATE VOLTS and MIN RATE VOLTS to the desired output range.
- The output only works when AHD is in use, an AHD call is active, Temp Dependent is set to Yes, and valid sensors are present.
- For a variable speed pump, connect the output to the pump's 0-10VDC input.
- Set VARIABLE SPEED MAX RATE VOLTS for high fire, VARIABLE SPEED MIN RATE VOLTS for low fire, and VOLTS WHEN BURNER OFF for burner-off operation.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: Weil-McLain Series 2 Condensing Gas Boiler Advanced Manual, p. 54. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.