Viessmann Boiler: Wire the CombiPLUS control and pump cables
Wire the CombiPLUS control and pump cables on a Viessmann boiler: Route and connect the control cable and pump cable to the CombiPLUS, then to the boiler power pump module.
Applies to: CombiPLUS A and Vitodens 100-W WB1B power pump module
How to fix wire the combiplus control and pump cables: step by step
- Remove both standard knock-outs on the rear right side of the CombiPLUS A. Route the control cable through one and the pump cable through the other, then secure them with the locknuts.
- Connect the electrical connectors inside the CombiPLUS: pump, diverting valve motor, flow sensor and water temperature sensor.
- At the power pump module, route the control cable through the fourth hole in the base and the pump cable through the second hole, then secure them with locknuts.
- Connect pump cable wires: black 1 (neutral) to X3 neutral, black 2 (line) to X3 line, and green/yellow ground to any open terminal on X2.
- Connect the five-pin DHW temperature sensor/flow sensor connector to X7 and the six-pin diverter valve connector to X10.
- Install the anchors and the conduit clip behind the cables, then press both cables into the clip.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Vitodens 100-W WB1B installation and service instructions, p. 29, p. 32. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.